> ## Documentation Index
> Fetch the complete documentation index at: https://docs.supplyline.com/docs/llms.txt
> Use this file to discover all available pages before exploring further.

# Overview

> The Walchem Intuition-6 is a flexible water treatment controller for cooling towers, boilers, and process applications

# Walchem Intuition-6 Controller

<sub>Source: [Intuition-6 Instruction Manual Rev. H](https://supplyline.com/assets/wal/WAL-IOM_Intuition-6-Instruction-Manual-RevH.pdf), Pages: 1–6</sub>

The Walchem Intuition-6 Series controller is a microprocessor-based measuring and control instrument designed for water treatment applications. It combines flexible sensor inputs with powerful control algorithms to manage chemical dosing, blowdown, and monitoring across cooling towers, boilers, and industrial process systems.

<Frame caption="Intuition-6 controller with 5-inch color touchscreen">
  <img src="https://mintcdn.com/supplyline/iflbDbrEUDCOz-QA/images/wal/i6/front-panel-home-screen.jpg?fit=max&auto=format&n=iflbDbrEUDCOz-QA&q=85&s=95ddb7e0c0e2ba418ce4589f091d9904" alt="Intuition-6 front panel showing touchscreen home screen with sensor inputs and relay outputs" width="906" height="547" data-path="images/wal/i6/front-panel-home-screen.jpg" />
</Frame>

## Product Family

The Intuition-6 is available in application-specific configurations, each optimized with pre-configured sensor and control options:

| Model | Application         | Typical Use                                            |
| ----- | ------------------- | ------------------------------------------------------ |
| WCT6  | Cooling Tower       | Conductivity blowdown, inhibitor feed, biocide control |
| WBL6  | Boiler              | Blowdown control, condensate monitoring                |
| WDS6  | Disinfection        | Chlorine, bromine, ClO₂, ozone, PAA control            |
| WPH6  | pH Control          | Acid/base neutralization, pH adjustment                |
| WCN6  | Conductivity        | General conductivity monitoring and control            |
| WPD6  | Pyxis Oxidizer + pH | Fluorometer-based oxidizer with pH monitoring          |

<Tip>
  All models share the same controller hardware and firmware. The model designation determines the pre-configured sensor packages and mounting options available when ordering.
</Tip>

## Key Capabilities

<CardGroup cols={2}>
  <Card title="Sensor Inputs" icon="gauge">
    One or two sensor inputs supporting conductivity, pH, ORP, disinfection sensors, and 4-20 mA transmitters
  </Card>

  <Card title="Control Outputs" icon="toggle-on">
    Up to six relay outputs with powered, dry contact, or pulse solid state options
  </Card>

  <Card title="Digital Inputs" icon="circle-nodes">
    Six digital input channels for flow switches, water meters, and feed monitors
  </Card>

  <Card title="Connectivity" icon="ethernet">
    Ethernet for web access, email alerts, Modbus TCP, and BACnet integration
  </Card>
</CardGroup>

## Sensor Compatibility

| Sensor Type                | Description                                                            |
| -------------------------- | ---------------------------------------------------------------------- |
| Contacting Conductivity    | 0.01, 0.1, 1.0, or 10.0 cell constant                                  |
| Electrodeless Conductivity | For high-conductivity or coating applications                          |
| pH and ORP                 | Preamplified signals (WEL/WDS series)                                  |
| Disinfection               | Free chlorine, total chlorine, chlorine dioxide, ozone, peracetic acid |
| Generic Sensors            | Ion Selective Electrodes or linear voltage outputs                     |
| 4-20 mA Transmitters       | Fluorometers, corrosion monitors, flow meters                          |

## Control Output Options

| Output Type                   | Rating                        | Use Case                        |
| ----------------------------- | ----------------------------- | ------------------------------- |
| Powered Mechanical Relays     | 6 A resistive, fused as group | Direct pump/valve control       |
| Dry Contact Mechanical Relays | 6 A resistive, not fused      | External power source switching |
| Pulse Solid State Opto        | 200 mA, 40 VDC max            | Proportional and PID control    |
| 4-20 mA Analog (optional)     | 600 Ω max load                | Variable speed pumps, valves    |

## Control Modes

The Intuition-6 includes over 20 control algorithms covering virtually every water treatment scenario:

<Tabs>
  <Tab title="Basic Control">
    | Mode           | Description                       |
    | -------------- | --------------------------------- |
    | On/Off         | Single set point with deadband    |
    | Dual Set Point | Control within or outside a range |
    | Manual         | Relay activates only in Hand mode |
  </Tab>

  <Tab title="Proportional">
    | Mode               | Description                               |
    | ------------------ | ----------------------------------------- |
    | Time Proportional  | On-time proportional to error             |
    | Pulse Proportional | Pulse rate proportional to error          |
    | PID                | Standard proportional-integral-derivative |
  </Tab>

  <Tab title="Timer-Based">
    | Mode          | Description                           |
    | ------------- | ------------------------------------- |
    | Timer         | Scheduled daily/weekly events         |
    | Biocide Timer | Pre-bleed and bleed lockout           |
    | Probe Wash    | Scheduled sensor cleaning             |
    | Spike         | Periodic shock to alternate set point |
  </Tab>

  <Tab title="Flow-Based">
    | Mode              | Description                        |
    | ----------------- | ---------------------------------- |
    | Flow Timer        | Feed after set volume passes       |
    | Flow Proportional | PPM dosing based on flow rate      |
    | Flow Meter Ratio  | Volumetric cycles of concentration |
  </Tab>

  <Tab title="HVAC/Boiler">
    | Mode                  | Description                             |
    | --------------------- | --------------------------------------- |
    | Bleed & Feed          | Simultaneous blowdown and chemical feed |
    | Bleed then Feed       | Feed as percentage of bleed time        |
    | Intermittent Sampling | Trapped sample boiler blowdown          |
  </Tab>
</Tabs>

<Note>
  Some control modes require specific hardware configurations. Pulse proportional and PID control require opto relay outputs. Analog control modes require the optional 4-20 mA output card.
</Note>

## Connectivity Options

Use these options to connect the controller to local networks or remote services.

### Ethernet

Remote access via direct connection, LAN, or Walchem Fluent cloud service:

* Web-based configuration and monitoring
* Email alerts and datalog reports
* Modbus TCP and BACnet integration
* Remote sensor calibration

<Accordion title="Walchem Fluent Cloud Platform">
  Walchem Fluent is a cloud-based water treatment management platform that extends controller capabilities:

  * **Real-time monitoring** — Access controller data from any device
  * **Alarm management** — Prioritized alarms with escalation and acknowledgment
  * **Data visualization** — Interactive graphs with historical trending
  * **Multi-site management** — Organize customers and facilities in a single dashboard
  * **Team permissions** — Admin, technician, and view-only user roles

  Fluent connects to Intuition-6 controllers via the Ethernet option.
</Accordion>

### USB

Local utility functions:

* Firmware upgrades
* Configuration file backup and transfer
* Datalog export to spreadsheet format

## Virtual Inputs and Outputs

The controller provides six virtual inputs and six virtual control outputs for advanced applications:

<Accordion title="Virtual Input Calculations">
  Virtual inputs can calculate values from physical sensors:

  * **Difference** — Input 1 minus Input 2
  * **Ratio** — Input 1 divided by Input 2 (cycles of concentration)
  * **Total** — Input 1 plus Input 2
  * **% Difference** — Percent rejection calculations
  * **Redundant** — Primary/Backup or Min/Max sensor selection
</Accordion>

<Accordion title="Virtual Output Uses">
  Virtual outputs implement control algorithms that can interlock or activate physical outputs, conserving relay resources for complex control schemes.
</Accordion>

## Typical Applications

<CardGroup cols={2}>
  <Card title="Cooling Tower Control" icon="fan">
    * Conductivity-based blowdown with inhibitor feed
    * Biocide timer programs with pre-bleed
    * Flow proportional chemical dosing
    * Cycles of concentration monitoring
  </Card>

  <Card title="Boiler Blowdown" icon="fire">
    * Intermittent sampling with trapped sample
    * Continuous or proportional blowdown
    * Surface and bottom blowdown coordination
  </Card>

  <Card title="Disinfection Control" icon="droplet">
    * Chlorine/bromine residual control
    * ORP-based oxidant control with spike events
    * pH-chlorine combination sensors
    * EPA Method 334.0 compliant chlorine reporting
  </Card>

  <Card title="Process Control" icon="industry">
    * pH adjustment with proportional or PID
    * Corrosion inhibitor dosing
    * Tagged tracer (PTSA/polymer) monitoring
  </Card>
</CardGroup>

<Frame caption="Typical cooling tower installation with Intuition-6 controller">
  <img src="https://mintcdn.com/supplyline/iflbDbrEUDCOz-QA/images/wal/i6/cooling-tower-installation.jpg?fit=max&auto=format&n=iflbDbrEUDCOz-QA&q=85&s=90806cc40465db90e4687587d42f8729" alt="Cooling tower system diagram showing controller, metering pumps, sensors, and flow switch manifold" width="1363" height="1603" data-path="images/wal/i6/cooling-tower-installation.jpg" />
</Frame>

## Physical Characteristics

| Specification         | Value                                                       |
| --------------------- | ----------------------------------------------------------- |
| Enclosure             | Polycarbonate, NEMA 4X (IP66)                               |
| Display               | 5" TFT color touchscreen (800 x 480 pixels), multi-language |
| Dimensions            | 11.1" x 8.3" x 5.5" (282 x 211 x 140 mm)                    |
| Operating Temperature | -4 to 131°F (-20 to 55°C)                                   |
| Power                 | 100-240 VAC, 50/60 Hz                                       |

## What's Included

Each Intuition-6 controller ships with:

* Controller with installed option cards per order
* Instruction manual
* Power cord (prewired models) or conduit fittings (hardwired models)

<Warning>
  The controller contains live circuits even when the front panel power switch is OFF. Always disconnect power at the source before opening the enclosure.
</Warning>

***

## Related Documentation

<CardGroup cols={2}>
  <Card title="Specifications" icon="list-check" href="/docs/wal/i6/specifications">
    Detailed measurement and electrical specifications
  </Card>

  <Card title="Installation" icon="wrench" href="/docs/wal/i6/installation">
    Mounting, sensor installation, and wiring diagrams
  </Card>

  <Card title="Programming Guide" icon="sliders" href="/docs/wal/i6/programming">
    Complete control mode reference for all relay algorithms
  </Card>

  <Card title="Operation" icon="hand-pointer" href="/docs/wal/i6/operation">
    Touchscreen interface and menu navigation
  </Card>
</CardGroup>

## Sources

<Card title="Intuition-6 Instruction Manual Rev. H" icon="file-pdf" href="https://supplyline.com/assets/wal/WAL-IOM_Intuition-6-Instruction-Manual-RevH.pdf" horizontal>
  Pages 1–6 • February 2024
</Card>