Source: Intuition-6 Brochure, Pages: 5–6 The Intuition-6 model code specifies the controller configuration, relay types, sensor inputs, and included sensors. Use this guide to build the correct model number for your application.

Model Code Structure

WCT6 - A00 - P - AA - A - M - P - ABNN
│      │     │   │    │   │   │   └── Sensors (4 characters)
│      │     │   │    │   │   └────── Sensor Mounting
│      │     │   │    │   └────────── Ethernet Option
│      │     │   │    └────────────── Analog Outputs
│      │     │   └─────────────────── Input Boards (2 characters)
│      │     └─────────────────────── Power Cord
│      └───────────────────────────── Relays/Wiring
└──────────────────────────────────── Base Model (Application)

Base Model Selection

Choose the base model that matches your primary application:
ModelApplicationDescription
WCT6Cooling TowerConductivity blowdown, inhibitor feed, biocide timers
WBL6BoilerBlowdown control, condensate monitoring, high-temp sensors
WDS6DisinfectionAmperometric sensors for chlorine, ClO₂, ozone, PAA
WPH6pH ControlpH/ORP measurement and control
WCN6ConductivityGeneral conductivity monitoring and control
WPD6Pyxis Oxidizer + pHFluorometer-based oxidizer with pH monitoring
All base models use the same controller hardware. The model designation determines available sensor packages and pre-configured control algorithms.

Relays and Wiring

CodeDescription
0006 powered relays
1002 powered + 4 dry contact relays
2002 opto + 4 dry contact relays
4004 opto + 2 dry contact relays
A006 powered relays with USA pigtails prewired
B002 powered relays with USA pigtails prewired + 4 dry contact
C002 opto relays with 20 ft pulse cables + 4 dry contact
D004 opto relays with 20 ft pulse cables + 2 dry contact
Prewired options (A00, B00, C00, D00) simplify installation. Opto relay outputs are required for pulse proportional and PID control modes.

Power Cord

CodeDescription
PUSA power cord
DDIN power cord (European)
BBrazil power cord
HHardwired (no power cord)

Input Boards

Select two input board codes in alphabetical order (e.g., “AA”, “AB”, “BC”):
CodeDescription
AOne sensor input board (conductivity, pH/ORP, disinfection)
BOne dual analog input board (two 4-20 mA channels)
COne combination sensor + analog input board
NNo sensor input board
Electrodeless conductivity sensors require the “A” sensor input board and will not work with the “C” combination board.
Common Configurations:
CodeConfiguration
AATwo sensor inputs (e.g., conductivity + pH)
ABOne sensor + two analog inputs (e.g., conductivity + fluorometer)
BBFour analog inputs
CCTwo combination boards (two sensors + two analog)
ANOne sensor input only

Analog Outputs

CodeDescription
NNo analog outputs
AOne dual isolated 4-20 mA output card

Ethernet Option

CodeDescription
NNo Ethernet
EEthernet board (web access, email alerts)
MEthernet board with Modbus TCP + BACnet

Sensor Mounting

Mounting options vary by base model:
CodeDescription
NNo flow switch, no mounting hardware, no sensors
SSubmersion sensors, 20 ft cables (no flow switch)
IInline sensors, 20 ft cables (no flow switch)
LLoose flow switch manifold, 20 ft cables, low pressure
PFlow switch manifold on panel, 3 ft cables, low pressure
FLoose flow switch manifold, 4 ft cable, high pressure
HFlow switch manifold on panel, 4 ft cables, high pressure

Sensor Selection

Select sensor codes based on your base model. Choose the specified number of characters in alphabetical order, with “N” (no sensor) last if fewer sensors are needed.
Choose 4 codes in alphabetical order (except N last)
CodeSensor
AGraphite contacting conductivity
B316SS contacting conductivity
CElectrodeless conductivity
DHigh pressure contacting conductivity
EGraphite conductivity for makeup water (threaded adapter)
FFlat surface WEL pH, no ATC
GHigh pressure pH, no ATC
HRod style WEL ORP
IFlat surface WEL ORP
JHigh pressure ORP
KFree chlorine, 20 ppm, extended pH range membrane
LChlorine dioxide 0-20 ppm membrane
MLittle Dipper 2, 0-200 ppb PTSA (analog)
NNo sensor
PPyxis PTSA (analog)
SDisinfection membrane, no sensor
TPyxis Tagged Polymer (analog)
UPyxis PTSA + Tagged Polymer (2 analog)
VFlat surface WEL pH, 4-20 mA (analog)
WRod style WEL ORP, 4-20 mA (analog)
XFlat surface WEL ORP, 4-20 mA (analog)
Dipper, Pyxis, chlorine, ClO₂, and disinfection sensors are not available with submersion mounting. Electrodeless conductivity requires “A” sensor input board.

Example Model Codes

Model CodeDescription
WCT6-A00-P-AA-N-M-P-ABNNCooling tower: 6 powered relays prewired, USA cord, 2 sensor inputs, Ethernet+Modbus, panel-mount low pressure manifold, graphite cond + SS cond
WBL6-000-H-AA-A-E-ANBoiler: 6 powered relays hardwired, 2 sensor inputs, dual analog out, Ethernet, boiler sensor with ATC
WDS6-C00-P-AC-N-M-P-ABDisinfection: 2 opto + 4 dry, USA cord, sensor + combo board, Ethernet+Modbus, panel manifold, free chlorine + ClO₂
WPH6-A00-P-AA-N-E-I-BCNNpH control: 6 powered prewired, 2 sensor inputs, Ethernet, inline sensors, flat pH + flat pH no ATC

Compatible Accessories

For flow switches, sample panels, and additional sensors, see the Walchem accessories catalog or contact your distributor.

Sources

Intuition-6 Brochure

Pages 5–6