Skip to main content

Troubleshooting

Source: Intuition-6 Instruction Manual Rev. H, Pages: 103–110 This section covers common issues and their solutions. For problems not covered here, contact technical support with the controller model, software version, and alarm history.

Calibration Failures

Use these symptom tables to diagnose calibration errors by sensor type.

Contacting Conductivity Sensors

Electrodeless Conductivity Sensors

pH Sensors

ORP Sensors

Disinfection Sensors

Analog Inputs (4-20 mA)

Temperature Sensors

Alarm Messages

Reference these tables for alarm meanings and recommended actions.

Sensor Alarms

Output Alarms

System Alarms

Control Issues

Use these checks when outputs do not behave as expected.

Relay Won’t Turn On

1
Check HOA State — Must be in Auto for automatic control
2
Check Set Point — Process value must exceed set point (force lower) or be below (force higher)
3
Check Interlocks — Any interlocked input will prevent activation
4
Check Output Timeout — May need to reset after previous timeout

Relay Won’t Turn Off

1
Check HOA State — If in Hand, relay stays on until time limit or manual change
2
Check Deadband — Value may still be in control range
3
Check Off Delay — Relay may be in off delay period
4
Check Activate With — Another channel may be holding relay on

Poor Control (Overshooting/Undershooting)

For On/Off Control:
  • Increase deadband to reduce hunting
  • Add off delay to prevent rapid cycling
  • Add on delay if chemical reaction is slow
  • Enable duty cycling for slow-responding systems
For Proportional/PID Control:
  • Reduce gain for less aggressive response
  • Increase integral time for slower integration
  • Reduce proportional band for faster response (may increase overshoot)
  • Verify sensor is in representative location

Flow Timer Not Triggering

1
Verify flow meter is receiving pulses (check digital input status)
2
Check Volume/Contact setting matches flow meter specifications
3
Verify K-factor is correct for paddlewheel meters
4
Check for wiring issues (contact closure vs. hall effect)

Biocide Timer Not Running

1
Verify current day/time is correct in controller
2
Check event schedule matches intended days
3
Verify interlocks are not blocking execution
4
Check Add Last Missed setting if events seem skipped

Diagnostic Lights

The controller has diagnostic LEDs visible when the front panel is open:
LEDs are only visible with front panel open. Do not operate controller with panel open while powered.

Communication Troubleshooting

Follow these network and protocol checks for connectivity issues.

Ethernet Not Connecting

1
Verify cable is connected and linked (LED on)
2
Check IP settings (DHCP or static)
3
Ping controller IP from computer
4
Verify subnet mask matches network
5
Check gateway if accessing from different subnet

Web Pages Won’t Load

1
Verify browser is accessing correct IP address
2
Try different browser or clear cache
3
Check password (default shown on label)
4
Verify Ethernet settings haven’t changed

Email Not Sending

1
Verify network connectivity
2
Check SMTP server address and port
3
Verify authentication credentials
4
Check firewall/security settings
5
Test with simpler mail server if possible

Modbus Communication Fails

1
Verify slave address settings
2
Check baud rate and parity match
3
Verify register addresses
4
Use Modbus polling tool to test
5
Check wiring for RS-485 connections

Sensor-Specific Issues

Use these fixes for common sensor behavior changes.

pH Reading Drifts Between Calibrations

  • Increase calibration frequency
  • Check for process contamination
  • Verify proper sensor installation (U-trap, immersion)
  • Consider replacing electrode if slope is declining

Conductivity Reading Fluctuates

  • Check for air bubbles in sample line
  • Increase smoothing factor in settings
  • Verify temperature compensation settings
  • Check for stray electrical currents (electrodeless)

Disinfection Reading Drops to Zero

  • Verify sample flow through sensor
  • Check for membrane tear or fouling
  • Confirm membrane cap has adequate electrolyte
  • Ensure no back pressure on flow cell outlet

ORP Reading Unstable After Cleaning

  • ORP electrodes need time to stabilize
  • Immerse in process water for 30+ minutes
  • Consider that ORP inherently varies more than other measurements

When to Contact Support

Contact Walchem technical support if:
  • Calibration failures persist after electrode replacement
  • Controller displays error codes not in this manual
  • Repeated fuse failures occur
  • Display is blank or corrupted
  • Controller restarts unexpectedly
  • Control behavior is erratic despite correct programming
Information to have ready:
  • Controller model number (on label)
  • Software version (Configuration → Global Settings)
  • Complete alarm history
  • Description of symptoms and when they started
  • Recent changes to system or settings

Sources

Intuition-6 Instruction Manual Rev. H

Pages 103–110 • February 2024